1. Home
  2. Cable catalogue
  3. Power cable
  4. 0.6/1 kV XLPE Insulated Cable

0.6/1 kV XLPE Insulated Cable

YJV · YJLV

  • IEC 60502-1
  • GB/T 12706.1
0.6/1 kV XLPE Insulated Cable
Representative drawing of the cable construction, not to scale.

At a glance

Rated voltage0.6/1 kV
StandardIEC 60502-1
Operating temperature90 °C
Short-circuit temperature250 °C

Application

0.6/1 kV XLPE cable is used in indoor and outdoor installations, and in tunnels, cable trenches and ducts. The cable withstands external mechanical forces, but not tensile force during pulling.

Construction

ConductorCopper or aluminium
InsulationCross-linked polyethylene (XLPE)
ArmourUnarmoured, steel tape, or steel wire
Outer sheathPVC
Sheath colourBlack, or to order

Construction, layer by layer

ConductorPlain annealed copper, or aluminium. Stranded, class 2 to IEC 60228.
InsulationCross-linked polyethylene (XLPE). 90 °C continuous, 250 °C on short circuit.
Core identificationBrown, black and grey. Green/yellow earth core where a fourth or fifth core is supplied.
FillerPolypropylene, laid up with the cores to bring the cable round.
Inner sheathExtruded PVC bedding over the laid-up cores.
Outer sheathPVC, type ST2. Black as standard; other colours and printing to order.

Product types

XLPE/PVCXLPE insulated power cable, PVC sheathed
XLPE/STA/PVCXLPE insulated power cable, steel tape armoured, PVC sheathed
XLPE/SWA/PVCXLPE insulated power cable, steel wire armoured, PVC sheathed
FR/XLPE/PVCFlame-retardant XLPE insulated cable, PVC sheathed
FR/XLPE/STA/PVCFlame-retardant cable, steel tape armoured, PVC sheathed
FR/XLPE/SWA/PVCFlame-retardant cable, steel wire armoured, PVC sheathed

FR — flame retardant

Number of cores and nominal cross-sectional area

Values in square millimetres (mm²).

Single core

  • 1×4
  • 1×6
  • 1×10
  • 1×16
  • 1×25
  • 1×35
  • 1×50
  • 1×70
  • 1×95
  • 1×120
  • 1×150
  • 1×185
  • 1×240
  • 1×300
  • 1×400
  • 1×500

Two cores

  • 2×4
  • 2×6
  • 2×10
  • 2×16
  • 2×25
  • 2×35
  • 2×50
  • 2×70
  • 2×95
  • 2×120
  • 2×150
  • 2×185

Three cores

  • 3×4
  • 3×6
  • 3×10
  • 3×16
  • 3×25
  • 3×35
  • 3×50
  • 3×70
  • 3×95
  • 3×120
  • 3×150
  • 3×185
  • 3×240
  • 3×300

Three cores + earth

  • 3×4+1×2.5
  • 3×6+1×4
  • 3×10+1×6
  • 3×16+1×10
  • 3×25+1×16
  • 3×35+1×16
  • 3×50+1×25
  • 3×70+1×35
  • 3×95+1×50
  • 3×120+1×70
  • 3×150+1×70
  • 3×185+1×95
  • 3×240+1×120
  • 3×300+1×150

Three cores + two reduced

  • 3×4+2×1.5
  • 3×6+2×4
  • 3×10+2×6
  • 3×16+2×10
  • 3×25+2×16
  • 3×35+2×16
  • 3×50+2×25
  • 3×70+2×35
  • 3×95+2×50
  • 3×120+2×70
  • 3×150+2×70
  • 3×185+2×95
  • 3×240+2×120
  • 3×300+2×150

Four cores

  • 4×4
  • 4×6
  • 4×10
  • 4×16
  • 4×25
  • 4×35
  • 4×50
  • 4×70
  • 4×95
  • 4×120
  • 4×150
  • 4×185
  • 4×240
  • 4×300

Four cores + earth

  • 4×4+1×2.5
  • 4×6+1×4
  • 4×10+1×6
  • 4×16+1×10
  • 4×25+1×16
  • 4×35+1×16
  • 4×50+1×25
  • 4×70+1×35
  • 4×95+1×50
  • 4×120+1×70
  • 4×150+1×70
  • 4×185+1×95
  • 4×240+1×120

Five cores

  • 5×2.5
  • 5×4
  • 5×6
  • 5×10
  • 5×16
  • 5×25
  • 5×35
  • 5×50
  • 5×70
  • 5×95

Service conditions

Maximum conductor temperature in service90 °C
Short-circuit temperature250 °C — for no more than 5 seconds
Ambient temperature — in air40 °C
Ambient temperature — underground25 °C
Depth of direct burial80 cm
Thermal resistivity of soil1.2 °C·cm/W
Minimum ambient temperature when laying0 °C

Standards

  • IEC 60502-1
  • GB/T 12706.1

Made by ZMS Cable to the standard named above; the construction can be adapted to a project specification. Every batch is tested before shipment and ships with its test report.