PVC or LSZH? A difference that only shows on the day of a fire
The two cables behave identically for their whole service life. What separates them only appears in the minutes when people are trying to get out.
What happens in a fire
A PVC sheath burning releases hydrogen chloride and thick black smoke. The chloride combines with moisture in the air to form hydrochloric acid: it attacks lungs, and it corrodes electronics throughout a building rather than only where the fire is.
The smoke itself is the leading killer in building fires, not the flame. A sheath that blacks out an escape corridor kills more people than the fire does.
What LSZH means
Low Smoke Zero Halogen: a halogen-free compound that produces far less smoke and no acid gases. The standards it is measured against are IEC 60754 for combustion gases, IEC 61034 for smoke density, and IEC 60332 for flame propagation.
One distinction is widely confused. LSZH is about what comes off the cable when it burns. Fire-resistant (IEC 60331) is about the cable continuing to work during a fire. A fire pump and an alarm circuit need the second, not the first.
Where it is required
Tunnels, metro, airports, hospitals, shopping centres, server rooms, ships — any enclosed space people walk out of. In many of these the local code requires it, so the choice is not a choice.
What it costs
LSZH is more expensive, less flexible in cold, and less resistant to water and oil than PVC. In a buried duct outdoors there is no reason for it. The working rule: if people will walk past where the cable runs, the answer is LSZH.