OPGW, ADSS or OPPC? Choosing an optical cable for a power line
Three optical cables hang on transmission towers. What separates them is not the fibre but where it hangs, and whether the line must come off to fit it.
OPGW — in the earth wire position
Fibre inside a metal tube that also does the job of the overhead earth wire at the top of the tower. It is the usual choice on new transmission lines because it solves two problems with one component: lightning protection and data.
The constraint is that it occupies the earth wire position, so installing it on an existing line means taking the line out of service. On a working circuit that alone can rule it out.
ADSS — self-supporting, no metal
An all-dielectric cable that carries its own weight with no metallic element at all. It hangs below the power conductors and can be installed live, which is its decisive advantage on a network that cannot be switched off.
What to watch is dry-band arcing: in a high electric field the sheath degrades over time. The hanging position is therefore chosen by calculating the space potential, and an arc-resistant sheath is used above 110 kV.
OPPC — fibre inside the phase conductor
Combines the fibre and the conductor in one body that carries current. Used where there is no room for another wire: single-circuit distribution lines and crowded towers.
The least common and the most demanding at the joints, because every optical splice is also a splice on a live conductor.
Choosing in practice
New line, or a refurbishment where an outage is possible: OPGW. A working line that cannot be switched off: ADSS. No room for an extra wire at all: OPPC.