HTLS conductor: what it is and how to choose one

A transmission line at its limit does not have to be rebuilt. An HTLS conductor can nearly double its capacity on the towers already standing.

2025-07-30All articles

What an HTLS conductor is

HTLS stands for High Temperature Low Sag: a conductor that runs far hotter than a conventional one without sagging as far. ACSR begins to sag unacceptably at around 90 °C. HTLS conductors operate at 150-250 °C, and some higher still.

The practical consequence is simple. Power carried is proportional to current, and current is limited by the temperature the conductor reaches before its sag encroaches on ground clearance. Raise the temperature ceiling and the power ceiling rises with it.

Why it is chosen over rebuilding

Because the towers and foundations are the expensive, slow part. Replacing only the conductor on an existing structure can nearly double a line's capacity with no new land, no new right of way, and none of the years a new corridor spends in permitting.

That is what was done on the K-Electric project in Pakistan, where the existing conductors were replaced with high-performance STACIR/AW.

The main types

ACCC — a carbon and glass fibre composite core. The lightest and highest capacity, the most expensive, and the least forgiving to install: the core does not tolerate a sharp bend.

ACSS — annealed aluminium carried on a steel core. The steel takes the whole mechanical load, so the aluminium can run hot without losing strength. The simplest of the family and the closest to ACSR to install.

GTACSR and GZTACSR — the gap type. A greased gap between the aluminium and the steel core lets the two layers expand independently, so sag is governed by the steel alone. Excellent sag behaviour, slower to install, and it needs a trained crew.

STACIR/AW — an aluminium-clad Invar alloy core, the lowest thermal expansion of the group. Runs to 210 °C with very little sag.

How to choose

Start from the operating temperature you need, then from the mechanical tension the existing towers can take. A lighter conductor means less tension at the tower, and that is sometimes the governing constraint rather than temperature.

Then the environment: proximity to the sea argues for aluminium cladding over galvanised steel. Finally the skill available to install it — the gap type gives the best sag performance and punishes an untrained crew.

We supply all four to IEC 61089 and ASTM, and manufacture to a project specification where one exists.