Ampacity is not the whole answer: what gets missed in cable sizing

An ampacity table gives you a correct number for the table's conditions. The trouble is that your project is rarely in the table's conditions.

2025-09-30All articles

The table assumes things

Every current-carrying capacity in IEC 60364-5-52 rests on a stated ambient temperature, a stated installation method, and one cable on its own. Change any of the three and the number changes, sometimes by a third.

Temperature first: a figure derived at 30 °C means little in a cable trench in the Gulf in summer. The correction factor at 50 °C for XLPE is around 0.82 — a cross-section that looked adequate on paper no longer is.

Grouping is the commonest mistake

Six cables in one trench do not each carry what one alone would: each heats its neighbour. The grouping factor for six touching cables can fall to 0.57. That is a larger effect than temperature, and it is forgotten more often.

Voltage drop governs before heat does

Over distance, the cross-section set by voltage drop is larger than the one set by heating. The usual limit is 4% of nominal to the last point of utilisation. Over two hundred metres at a meaningful load, that alone can move you up two sizes.

And short-circuit current

The conductor has to survive the fault current until the protective device clears it, rather than melting first. The usual check is S ≥ I√t / k. A cable correct for continuous load and wrong for fault current looks fine until the first fault.

The practical order

Size it four times — corrected ampacity, voltage drop, short-circuit withstand, and conductor protection — then take the largest. Send us the load, the run length, the installation method and the ambient temperature and we will return the calculation with the size.