Articles and technical guides

AAC or ACSR? Choosing the right overhead conductor

The difference is not conductivity but which part carries the mechanical load — and that decides which survives a coastal span or a mountain crossing.

2024-11-18All articles

The difference in one sentence

AAC is all-aluminium: excellent conductivity, modest mechanical strength. ACSR is aluminium strands around a galvanised steel core that carries the tension, so it holds longer spans and heavier wind and ice loading.

When AAC is right

Urban distribution and short spans between poles, where the required tension is low to begin with. Because it is aluminium with no steel in it, its corrosion resistance is better — which makes it the usual choice in coastal and salt-laden air.

AAAC is a step beyond: an aluminium alloy, mechanically stronger than AAC and lighter than ACSR, with corrosion resistance that stays high. A good answer on the coast when an AAC span will not reach.

When ACSR is right

Transmission, long spans, river and valley crossings, and anywhere the mechanical load is the governing constraint. The steel core takes the tension so the aluminium does its electrical job without being asked for strength it does not have.

The price is corrosion. Steel and aluminium in contact in salt air form a galvanic cell. Galvanising delays that; it does not remove it. Near the sea, AAAC or an aluminium-clad core is the better answer.

And ACAR in between

ACAR replaces the steel core with an aluminium alloy one: stronger than AAC, lighter than ACSR, and with no two dissimilar metals touching. A practical middle when neither extreme suits.

We supply all four to IEC 61089 and ASTM B231, B232, B399 and B524.

Originally published on zmscable.fr